Skip to content Skip to content

Site Report: Eareckson AS - TA616

Site Name: Eareckson AS - TA616
Address: NW of the Active Runway, Amchitka, AK 99546
File Number: 2649.38.001, 2649.26.021
Hazard ID: 26308
Status: Active
Staff: Erica Blake, 9074512182 erica.blake@alaska.gov
Latitude: 52.718638
Longitude: 174.098238
Horizontal Datum:WGS84

We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.

Problems/Comments

Site TA616, also referred to as Site CC001 is the site of the active vehicle refueling station located northwest of the active runway. The site includes two 20,000-gallon underground storage tanks (USTs), one containing gasoline* (Owner Tank ID 517-1; DEC Tank ID 49) and the other containing diesel (Owner Tank ID 517-2; DEC Tank ID 50), and a vehicle refueling area. (*There is a discrepancy in site documentation regarding the type of fuel contained in Tank 517-1. According to the DEC UST Program, Tank 517-1 contains diesel.) Both tanks are cathodically protected, double walled, and inspected every five years. Piping associated with these tanks is pressurized fiberglass reinforced plastic with secondary containment and piping release detection, and the tanks are filled from the surface rather than through pipelines. A drainage ditch with standing water is present on the north side of the USTs. GRO, DRO, and PAH concentrations have been detected in soil samples above the cleanup levels. Surface water samples contained concentrations of total aqueous hydrocarbons above the cleanup level. Sheen was observed on the surface water in the downgradient drainage ditch.

Action Information

Action Date Action Description DEC Staff
11/10/2014 Site Added to Database A new site has been added to the database Mitzi Read
11/10/2014 Leaking Underground Storage Tank Release Confirmed - Petroleum LUST site created in CSP database for source area TA616; Two 20,000-Gal USTs 517-1 and 517-2, 79699 Mitzi Read
11/21/2014 Exposure Tracking Model Ranking Initial ranking with ETM completed for source area id: 79699 name: TA616; Two 20,000-Gal USTs 517-1 and 517-2 Jessica Morris
10/22/2015 Update or Other Action The ADEC Contaminated Sites Program reviewed and commented on a draft scope of work for investigation, remedial process optimization, and long term management studies at several sites for Eareckson Air Station. Jessica Morris
8/31/2016 Site Characterization Workplan Approved The ADEC Contaminated Sites Program conditionally approved the 2016 Uniform Federal Policy - Quality Assurance Project Plan (UFP-QAPP) for Site Characterization at 14 Former POL Sites, Eareckson Air Station, Shemya Island, Alaska. The conditions for the UFP-QAPP are as follows: 1) We do not object to the long term monitoring work being completed as outlined in the UFP-QAPP; however ADEC cannot concur that efforts will be counted towards meeting the end point criteria outlined in the decision documents until an adequate monitoring program has been established. 2)The QAPP states that field screening results and field observations will be used to determine additional groundwater monitoring well locations. These locations should to be coordinated with ADEC. 3) The leaking underground storage tank (LUST) sites at Eareckson Air Station will need to be characterized and closed in accordance with LUST regulations that are included in 18 AAC 78. 4) The scope of work for this investigation may not be sufficient to fully characterize the sites listed in the work plan, and additional investigation may be necessary. Jessica Morris
11/14/2016 Site Visit ADEC staff travelled to Eareckson Air Station for 4 days to conduct site visits and become familiar with the ecology and topography of the island. Site visits were conducted to all pertinent sites and meetings were held to with ADEC and USAF to discuss a path forward for the sites. Jessica Morris
9/30/2017 Leaking Underground Storage Tank Cleanup Initiated - Petroleum Administrative action addition for grant reporting purposes. Evonne Reese
11/27/2017 Site Visit ADEC staff travelled to Eareckson Air Station for 3 days to conduct site visits and institutional control inspections. Site visits were conducted to all pertinent sites and meetings were held to with ADEC and USAF to discuss a path forward for the sites. Jessica Morris
2/23/2018 Update or Other Action The ADEC Contaminated Sites Program submitted comments on the Draft Site Characterization Report at 13 Former POL Sites, Phase I, Eareckson Air Station, Alaska. Jessica Morris
2/23/2018 Document, Report, or Work plan Review - other The ADEC Contaminated Sites Program provide comments on the Draft Site Characterization Report at 13 Former POL Sites, Phase I, Eareckson Air Station. Jessica Morris
5/2/2018 Document, Report, or Work plan Review - other The ADEC Contaminated Sites Program submitted comments on the Draft Remedial Process Optimization Report for Eareckson Air Station. The purpose of the report was to present an evaluation of the effectiveness of the current selected site remedies and make recommendations for optimization of an island-wide monitoring and management program for contaminated sites at Eareckson. ADEC had numerous comments on the document, and requested a project team meeting to further discuss a more effective and efficient program at Eareckson. Jessica Morris
2/4/2019 Site Characterization Workplan Approved The ADEC Contaminated Sites Program approved the Final Addendum Addendum Uniform Federal Policy – Quality Assurance Project Plan (UFP-QAPP) for Site Characterization at 13 Former POL Sites, Eareckson Air Station, Sheyma Island, Alaska. The QAPP Addendum was approved with the following conditions: 1)ADEC requests weekly field meetings during the effort. 2)the LUST regulations in 18 AAC 78 still need to be achieved. 3) the scope of work for this effort may not be sufficient to fully characterize the sites, and additional characterization may be necessary. Jessica Morris
4/27/2022 Update or Other Action On 4/27/2022 ADEC approved the Eareckson Air Station, Alaska, REMEDIAL PROCESS OPTIMIZATION REPORT dated April 2022. This Remedial Process Optimization (RPO) Report presents an evaluation of the effectiveness of current selected site remedies and makes recommendations for optimization of the IWM Program, as appropriate to establish a more integrated groundwater monitoring program at Eareckson AS. RPO is a systematic approach for evaluating and improving the effectiveness of site remediation without increasing site risk. This RPO Report presents a site-by-site evaluation of effectiveness of the sites selected remedy and provides recommendations to: • Streamline groundwater monitoring. • Develop a holistic approach to site management. • Maintain the remedial action objectives (RAOs) set forth in established Record of Decisions (RODs) and Decision Documents (DDs). Daniela Fawcett
6/27/2023 Document, Report, or Work plan Review - other DEC provided comments for the Draft Final 2021 Long Term Management, Land Use and Institutional Controls Report Eareckson Air Station, Shemya, Alaska Sites CS566, DA002/DA002A, DA003, FT001, FT002, FT003, LF015, LF018, LF024, LF026, ML001, MU001, OD001, OT048, OT617, PL560, PL575, SS005, SS007, SS010, SS012, SS023, SS025, ST009, ST035, ST039, ST044, ST046, ST050, ST051, TA555, TA556, TA616, TU553, TU554, TU558, TU559, TU567, TU568, XU912, ZZ001, dated June 2023.The report describes the institutional control inspections and sampling efforts conducted during November 15 through November 30th, 2021. Forty-two different sites were investigated at the Eareckson Air Station located on Shemya Island, Alaska. Groundwater was sampled at nine sites, surface water was sampled at five sites, and sediment sampling was conducted at two sites. Contaminants above cleanup levels remain present at most sites with stable or non-discernable trends. Most land use controls appear to be in good condition and Monitoring and continued inspections were recommended for all sites. Ginna Quesada

Contaminant Information

Name Level Description Media Comments

Control Type

Type Details

Requirements

Description Details

There are no documents for this site report.

No associated sites were found.

Missing Location Data

Because the GIS location data for this site has not been entered, we cannot direct you to its position on the map. Click "Continue" to proceed to the Contaminated Sites Web Map or "Close" to return to the site report.
Continue     Close