Skip to content Skip to content

Site Report: Fort Greely Texas Condo Office Cmpl

Site Name: Fort Greely Texas Condo Office Cmpl
Address: 11 Miles S. of Ft. Greely, Cantonment Area, Fort Greely, AK 99731
File Number: 141.38.028
Hazard ID: 1166
Status: Active
Staff: Carly Jensen, 9072697558 carly.jensen@alaska.gov
Latitude: 63.816538
Longitude: -145.877629
Horizontal Datum:WGS84

We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.

Problems/Comments

1500 gallon diesel spill through broken underground fuel line on 11/2/90. Initial excavation discontinued at approximately 12 foot depth due to extensive evidence of more widespread contamination. Sampling in bottom of the excavation exhibited approximately 5000 ppm of hydrocarbon contamination. 140.38.008. Last staff assigned was Short. (rpltr7)

Action Information

Action Date Action Description DEC Staff
11/5/1990 Interim Removal Action Approved 1500 gallons of fuel spilled from underground line break. Initial excavation attempted to collect all contaminated soil. Unable to excavate all, sampled excavation, 5000 ppm diesel test result. Approximately 13 cubic yards of contaminated soil stockpiled. Dan Basketfield
6/1/1992 Update or Other Action (Old R:Base Action Code = SA1 - Phase I Site Assessment (General)). Contamination seeping out of bottom of hillside at site. Seep is hydraulically connected to surface water stream which flows to three shallow lakes nearby. Vadose zone contaminated. Free product detected at seep. Surface water contaminated. Dan Basketfield
2/1/1993 Site Characterization Report Approved (Old R:Base Action Code = SA1R - Phase I SA Review (CS/LUST)). Reviewed "Texas Condo Fuel Spill Site Characterization, 28, December 1992," Richard J. Mauser, Captain; MS, Environmental Science Officer, cold Regions Test Center, Fort Greely, Alaska. Dan Basketfield
2/5/1993 Meeting or Teleconference Held Met with base commander concerning site. Requested that further site assessment activity focus on corrective action. Focus on source material elimination, leachate minimization, control/containment of seep site to stream. Dan Basketfield
2/8/1993 Site Ranked Using the AHRM Initial ranking. Former Staff
2/12/1993 Site Added to Database Diesel. Former Staff
9/14/1993 Meeting or Teleconference Held Personnel from 6th Infantry Brigade, Cold Regions Test Center, and CRRL met with ADEC NRO staff to report progress, and discuss requirements. Bob Couch
5/16/1994 Update or Other Action (Old R:Base Action Code = RPL2 - Site Information Request Letter). Sent PRP-CS Database Notification Letter to Cristal Fosbrook requesting update/confirmation of information concerning the contaminated site. Jeff Peterson
12/6/1995 Update or Other Action Site is improving via natural attenuation. Monitoring continues by Army. Ronan Short
3/11/1996 Meeting or Teleconference Held Meeting with Fort Greely Staff-Captain, Macmanus, discussed final year of site monitoring of DRO hillside seep. Decision to continue monitoring will be made after analysis of June sampling results. Ronan Short
2/20/1998 Update or Other Action ADEC received a report from the Department of the Army. According to the report, sampling for 1997 revealed benzene, ethylbenzene, toluene and total xylenes levels in all water samples below the MCLs set forth in 18 AAC 080.70. Total BTEX and benzene levels in the soil were found to be below the Category C cleanup levels. They stated that CRTC will continue to monitor the site until soil cleanup levels are reached. Deborah Williams
5/15/2008 Exposure Tracking Model Ranking Initial ranking with ETM completed. Deborah Williams
11/10/2016 Exposure Tracking Model Ranking A new updated ranking with ETM has been completed for source area 72145 Broken fuel line. Melody Debenham

Contaminant Information

Name Level Description Media Comments

Control Type

Type Details

Requirements

Description Details

There are no documents for this site report.

No associated sites were found.

Missing Location Data

Because the GIS location data for this site has not been entered, we cannot direct you to its position on the map. Click "Continue" to proceed to the Contaminated Sites Web Map or "Close" to return to the site report.
Continue     Close