Action Date |
Action |
Description |
DEC Staff |
3/1/1991 |
Underground Storage Tank Site Characterization or Assessment |
SA1; Basketfield: Tighteness tested 10,000 gal. diesel tank at Maintainence Bldg. failed test due to electrical-type coupling that were leaking. |
Former Staff |
12/7/1992 |
Release Investigation |
RELR; Basketfield: Reviewed Shannon & Wilson 8-26-92 report "UST Site Assessment and Closure., NTP-1, 2301 Peger Rd, FBKS, AK". |
Former Staff |
1/8/1993 |
Update or Other Action |
CORR; Basketfield: Sent letter to Jim Little, ADOT Northern Region, discussing Shannon & Wilson's site assessment and further actions at the site. |
Former Staff |
2/23/1993 |
Update or Other Action |
RPL2; Peterson sent PRP-CS Database Notification Letter to RP requesting update and more environmental information concerning contaminated site. DOT/Clarke Milne will respond in month or two, but as of this complete date have rec'd no response! |
Former Staff |
9/21/1995 |
Underground Storage Tank Site Characterization or Assessment |
10,000-gallon & 3,000-gallon diesel UST removed with soil and grd water impact. |
Former Staff |
9/21/1995 |
Leaking Underground Storage Tank Cleanup Initiated - Petroleum |
entered by JC |
Former Staff |
5/24/1996 |
Update or Other Action |
UPD; USTs removed 9/95. Approx. 240 cu. yds. contam. soil thermally treated. Approx. 700 cu. yds. contam. soil still remain under/around dispenser area. Passive air venting system for soils installed. 5/96 quart. monitoring grd. water, Benzene @ MW 7 still high. Other MWs frozen @ 14 ft. bgs, no samples taken. |
Former Staff |
8/19/1997 |
Leaking Underground Storage Tank Corrective Action Underway |
Still high Benzene levels. (3) MWs sampled three times '96, twice '97, last sampling date 8/19/97. Upgradient MW=2.79 ppb Benzene. Two downgradient MWs 118 ppb & 10,400 ppb Benzene. Passive soil venting system indicates PID reading 280 ppm as of 8/97. Grd water movement carrying contam towards Davis Rd. poss moved beyond ADOT boundary. Lack of funding to continue cleanup |
Former Staff |
9/2/1998 |
Leaking Underground Storage Tank Release Confirmed - Petroleum |
LUST Site created in CSP for source area ID 78100 (Added by zt_qryAddLustStatus) |
Former Staff |
9/2/1998 |
Site Added to Database |
|
Former Staff |
1/28/2004 |
Update or Other Action |
Transferred DEC staff lead from John Carnahan |
Cynthia Pring-Ham |
7/7/2008 |
Exposure Tracking Model Ranking |
Intitial Ranking Complete for Source Area: 78100 (Autogenerated Action) |
|
8/7/2012 |
Update or Other Action |
Site transferred to Jim Fish. |
Janice Wiegers |
6/28/2013 |
Site Characterization Report Approved |
Recieved Vapor intrusion Assessment FY12 Report - SSD systems functioning in Materials Lab and Maintenance & Operations Building; see Peger Rd Facility (102.38.098). |
Jim Fish |
9/3/2015 |
Update or Other Action |
Met with ADOT Design staff & Environ Analyst for discussion of plans to construct Traffic Operation Center at the current M&O Building; discussed groundwater & soil gas contamination, and suggested installation of SSD & SVE system during construction. |
Jim Fish |
3/15/2016 |
Meeting or Teleconference Held |
Met with Design Alaska engineer and ADOT to discuss possible SVE system installation as part of M&O Building addition construction. |
Jim Fish |
11/29/2016 |
Update or Other Action |
Received an Environmental Assessment and Work Plan for excavation sampling and stockpile management for the proposed ADOT&PF Traffic Operations Center, as a building addition to the M&O Building. |
Jim Fish |
3/3/2017 |
Update or Other Action |
Met with consultant/designer for SSD system installation regarding environmental work plan review (prepared by subcontractor). DEC will provide comments for soil handling and disposal consideration; anticipate coordination with EPA RCRA program. |
Jim Fish |
5/9/2017 |
Update or Other Action |
Final sampling and analysis plan received and approved today. |
Jim Fish |
7/25/2017 |
Offsite Soil or Groundwater Disposal Approved |
Approx. 20 CU yd of DRO-contaminated soils approved for transport to OIT |
Jim Fish |
12/7/2017 |
Update or Other Action |
Monitoring report for soil excavations associated with building expansion received today.
See also file 102.38.098 |
Jim Fish |
4/17/2018 |
Exposure Tracking Model Ranking |
A new updated ranking with ETM has been completed for source area 78100 diesel USTs and dispensers. |
Jim Fish |
11/27/2018 |
Update or Other Action |
Received indoor air sampling results from October sampling even; VOCs detected, but below DEC Commercial indoor air target levels (some VOCs, i.e., benzene, are above residential target levels) |
Jim Fish |
4/5/2019 |
Update or Other Action |
TRFP is under development for vapor intrusion evaluation for the Bridge Shop (Current exposure). Additional onsite characterization, remediation, and offsite monitoring is pending for later efforts. |
Jim Fish |