Skip to content Skip to content

Site Report: FAA Fort Yukon Quarters Facility Bldg 101 UST 9-C-6

Site Name: FAA Fort Yukon Quarters Facility Bldg 101 UST 9-C-6
Address: Airport Vicinity, Fort Yukon, AK 99740
File Number: 740.38.011
Hazard ID: 25397
Status: Active
Staff: Brittani Mack, 9072628205 brittani.mack@alaska.gov
Latitude: 66.570446
Longitude: -145.240950
Horizontal Datum:WGS84

We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.

Problems/Comments

One underground storage tank was removed at this residence in 1995 as documented in the Fuel Storage Tank Decommissioning Assessments, dated 1995. Tank 9-C-6 was an active 500 gallon diesel tank that was removed and 15 cubic yards of petroleum-contaminated soil were removed. Six (6) confirmation samples were collected and analytical results showed that diesel-range organics concentrations up to 560 mg/kg remained. The department determines that with the low concentrations remaining that there is likely only a very small volume of contaminated soil in place. The department determines that no further remedial action is planned for the Building 101 former tank area. If, in the future, the building is removed and the soil at the former tank area is accessible, the area should be characterized and any contamination managed in accordance with department regulations and guidance, as required by 18 AAC 75.325(i).

Action Information

Action Date Action Description DEC Staff
7/15/1991 Site Added to Database A new site has been added to the database (Date adjusted from 4/10/2009 for report/query consistency. (Reese)) Mitzi Read
7/15/1991 Update or Other Action (Old R:Base Action Code = SA1 - Phase I Site Assessment (General)). Building 300 Floor drain and drum storage area on SE corner of building, and north and west sides of building show contamination. PAHs, heavy metals, and DRPH found at elevated levels. USTs are located at the NE and SE corners of the building. Building 601 Assessment (General)). Contaminated floor drain and drum storage area. Don Gibler
7/15/1992 Preliminary Assessment Approved Incinerator at Building 300. Phase I Site Assessment (General)). Soil samples collected next to incinerator concrete pad show dioxin and congeners, elevated levels of copper, lead and zinc. Don Gibler
10/9/1992 Interim Removal Action Approved (Old R:Base Action Code = SA1R - Phase I SA Review (CS/LUST)). Building 300 Interim action required of putting removable cap on floor drain. The use of this drum storage area has been discontinued. Asked that R.I. and C.A.P. be prepared ASAP. Building 601Interim action required - discontinue use of floor drain, cap with removable seal, place drums on impermeable liner, place leaking drums in overdrums and dispose of at H.W. facility, follow 18.AAC 68. Do R.I. and prepare C.A.P. ASAP. Building 300 incinerator. Interim Corrective action required: 1) curtail emissions or discontinue use of incinerator. Release investigation and Corrective action required ASAP. Don Gibler
10/9/1992 Update or Other Action Received the Environmental Compliance Investigation Report. Former Staff
5/12/1993 Site Added to Database Lead, DRPH and PAH contamination. Former Staff
5/15/1993 Site Ranked Using the AHRM Initial ranking. Former Staff
6/29/1994 Update or Other Action (Old R:Base Action Code = RPL2 - Site Information Request Letter). Sent PRP-CS Database Notification Letter to RP requesting update and more environmental information concerning contaminated site. RP/Jackie for FAA Anchorage office responded to let me know she will be sending information on the facilities soon. Received information on 8-8-94. Jeff Peterson
8/8/1994 Site Ranked Using the AHRM Reranked (Based on DDT contaminated soil in addition to CERCLA sources). Former Staff
11/27/1995 Update or Other Action Summary of meeting on 11/8/1995 and proposed corrective action approaches at three sites: Installation of bioremediation systems at FAA Fort Yukon Building 100 and the FAA Fort Yukon Health Clinic Building and landspreading of contaminated soils at FAA Fort Yukon RCAG Facility. Kent Patrick-Riley
11/27/1995 Update or Other Action FAA Fort Yukon Old FSS Facility located approximately 60 feet east of Building 100 and 20 feet south of the Yukon Flats Health Clinic. Contaminated soils left in place due to structural issues with the FSS building. NFRAP action changed to update on 11/7/02. The building may have been removed and the contaminated soils may be accessible. Kent Patrick-Riley
1/17/1996 Update or Other Action Received Underground Fuel Storage Tank (UST) Decommissioning Assessment Report for tanks: 9-C-1 - 9-C-4 at Building 300, 9-C-5 at Building 601, 9-C-7 at Building 100, 9-C-8 at the Old FSS, and 9-C-9 and 9-C-10 at the Yukon Flats Health Clinic. Contamination was left in place at Building 100, the Old FSS, and the Yukon Flats Health Clinic. Confirmation samples were not collected at the depth of the excavation at tank 9-C-3 at Building 300. Former Staff
7/29/1996 Update or Other Action Received the Site Cleanup and Investigation Report documenting sampling at Buildings 300 and 601. Former Staff
7/8/2002 Update or Other Action Adjusted priority and site location to reflect data provided in reports. Elizabeth Stergiou
7/9/2002 Site Number Identifier Changed Workplan changed from 09 to 01 to reflect no presence of hazardous substances above cleanup levels. Sequence Number changed from 04 to 01. Elizabeth Stergiou
7/16/2002 Update or Other Action Rec'd Memorandum from FAA consultant titled "Product Baildown Tests and Groundwater Sampling Near Yukon River at FAA Tanana Site, Alaska". Eileen Olson
9/18/2002 Update or Other Action Sent letter requesting groundwater monitoring for all existing wells on site, monitoring of the in-situ system, and monitoring of the landspread soil, with a schedule of monitoring to be submitted by March 31, 2003 and the monitoring to be complete by June 30, 2003. Elizabeth Stergiou
9/19/2002 Update or Other Action Sent general letter requesting the following documents be submitted by 10/1/02: status of groundwater monitoring and all groundwater monitoring reports since February 12, 1997, status of the in-situ remediation system and associated soil sand groundwater and all associated reports since February 12, 1997, status of the land spread treatment cell and associated soils and groundwater and all associated reports since February 12, 1997, and status of all contaminated sites at the station. Elizabeth Stergiou
11/21/2005 Update or Other Action Building 101: No Further Remedial Action Planned: Tank 9-C-6, a 500 gallon diesel tank, was removed along with 15 cubic yards of petroleum-contaminated soil in 1995. Six confirmation samples showed an elevated level of 560 mg/kg DRO remaining in-situ. If, in the future, the building is removed and the soil at the former tank area is accessible, the area should be characterized and any contamination managed in accordance with department regulations and guidance. ADEC letter sent November 21, 2005. Anne Marie Palmieri
8/31/2006 Site Characterization Workplan Approved Incinerator: site characterization workplan approved this date. Fieldwork is set to begin 9/7/06. Anne Marie Palmieri
4/24/2007 Site Characterization Report Approved The Final Site Investigation Report Federal Aviation Administration Former Incinerator Area Near Building 300, Fort Yukon, Alaska , March 14, 2007 was approved. Debra Caillouet
4/24/2007 Site Closure Approved Based on the Final Site Investigation Report Federal Aviation Administration Former Incinerator Area Near Building 300, Fort Yukon, Alaska , March 14, 2007, closure of the incinerator was approved. There are three additional sites within the Quarters facility requiring action and three requiring documentation of ICs to achieve conditional closure. Debra Caillouet
4/10/2008 Exposure Tracking Model Ranking Initial ranking with ETM completed. Debra Caillouet
4/10/2009 Exposure Tracking Model Ranking Initial ranking with ETM completed for source area id: 78759 name: Bldg 101 UST 9-C-6 Debra Caillouet
1/5/2016 Update or Other Action Site Transferred to PM Garroutte. Next actions are to perform a file review for site closure considerations and to contact FAA PM to confirm site status. Monte Garroutte
6/15/2017 Update or Other Action DEC sent FAA a memorandum regarding contamination at the Fort Yukon FAA Sites including Quarters Facility Buildings 100, 101, 102, 300, and 601, and associated USTs, Incineration Areas and interior sumps (Hazard IDs 25397,25393,25395, and 25396) to assist FAA with compliance with State of Alaska Contaminated Sites Cleanup Regulations. DEC-required actions for cleanup complete determinations for each AOC were spelled out in detail. John O'Brien

Contaminant Information

Name Level Description Media Comments

Control Type

Type Details

Requirements

Description Details
Hazard ID Site Name File Number
25393 FAA Fort Yukon Quarters Facility Bldg 300 Interior Sump 740.38.011
25395 FAA Fort Yukon Quarters Facility Bldg 601 Interior Sump 740.38.011
25396 FAA Fort Yukon Quarters Facility Bldgs 100 & 102 USTs 9-C-7, 9-C-9 & 9-C-10 740.38.011

Missing Location Data

Because the GIS location data for this site has not been entered, we cannot direct you to its position on the map. Click "Continue" to proceed to the Contaminated Sites Web Map or "Close" to return to the site report.
Continue     Close