Site Report: FNSB - Weller Elementary School UST 1
Site Name: | FNSB - Weller Elementary School UST 1 |
---|---|
Address: | 635 Elementary Drive, Fairbanks, AK 99712 |
File Number: | 100.26.202 |
Hazard ID: | 25535 |
Status: | Cleanup Complete |
Staff: | No Longer Assigned, 9074655229 dec.icunit@alaska.gov |
Latitude: | 64.887775 |
Longitude: | -147.592692 |
Horizontal Datum: | WGS84 |
We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.
Problems/Comments
In July, 2010 during the removal of a 5,000-gallon dual purpose (heating & emergency generator) diesel underground storage tank (UST #1), diesel was found to be leaking from the manway and fill pipe connection during overfilling. Approximately 70 cubic yards of contaminated soil were removed and stockpiled on a bermed liner pending treatment and disposal at Organic Incineration Technology, Inc. (OIT). Soil was excavated until bedrock was encountered. Field screening photoionization detector (PID) readings from the base of the excavation indicated petroleum compounds remaining at 350 parts per million (ppm). Laboratory analytical results were not yet available.
Action Information
Action Date | Action | Description | DEC Staff |
---|---|---|---|
5/20/2009 | Document, Report, or Work plan Review - other | DEC received and reviewed UST Site Assessment/Release Investigation/Corrective Action Plan (SA/RI/CAP) for the FNSB School District Areawide UST Improvements Project/Contract No. 08-SDGPRJ-01, prepared by Independent Consultants Associated (ICA). (MBarnes) | Janice Wiegers |
6/3/2009 | Update or Other Action | DEC emailed ICA comments and regulatory reminders for the SA/RI/CAP. (MBarnes) | Janice Wiegers |
7/15/2010 | Update or Other Action | FNSB notified DEC contaminated soil was found during tank removal. (MBarnes) | Janice Wiegers |
7/27/2010 | Site Added to Database | A new site has been added to the database | Mitzi Read |
7/27/2010 | Leaking Underground Storage Tank Release Confirmed - Petroleum | LUST site created in CSP database for source area UST #1 - 5,000-gallon Dual Purpose Diesel, 78923 | Mitzi Read |
7/27/2010 | Leaking Underground Storage Tank Cleanup Initiated - Petroleum | 3/2/11 - Administrative action addition | Evonne Reese |
7/27/2010 | Exposure Tracking Model Ranking | Initial ranking with ETM completed for source area id: 78923 name: UST #1 - 5,000-gallon Dual Purpose Diesel | Mitzi Read |
6/10/2011 | Document, Report, or Work plan Review - other | DEC received and reviewed Weller Elementary School Facility ID #3510 5,000-Gallon Diesel Underground Storage Tank Site Assessment/Tank Closure Report dated June 2011, prepared by ICA. The tank system was removed, recycled "as is" and disposed of at the GNI yard. A new regulated dual heating oil and emergency use 4,000-gallon double-walled diesel UST was installed in the save excavation. Approximately 161 cy of contaminated soil was hauled offsite for thermally remediation. Diesel contaminated soil remains onsite. (MBarnes) | Willett Boger |
1/31/2017 | Potentially Responsible Party/State Interest Letter | A PRP letter addressing several FNSB sites was mailed and the FNSB was notified. | Michael Hooper |
2/22/2017 | Meeting or Teleconference Held | Met with Borough Division of Public Works and briefly discussed the active FNSB CSP and LUST Sites. Preparing information request letter including 22 sites. | Michael Hooper |
3/20/2017 | Update or Other Action | Met with staff from ADEC drinking water. Was informed that the well at this school is no longer used for drinking water. Pioneer wells delivers potable water and the well is used for non-potable uses. | Michael Hooper |
4/25/2017 | Update or Other Action | Sent the FNSB a letter addressing 22 active CSP/UST sites. For Weller UST the letter requested information about abandoned UST piping and usage of groundwater. | Michael Hooper |
6/23/2017 | Update or Other Action | Received a letter from the Borough with a contractor cost estimate for a phase 1 project scoping and file review for all active Fairbanks North Star Borough sites. | Michael Hooper |
9/12/2017 | Update or Other Action | Received phonecall from FNSB deputy director of public works. A report containing the information requested in the April 21, 2017 letter should be coming by end of October. | Michael Hooper |
12/21/2017 | Update or Other Action | Received memo with site summary in response to ADEC letter dated April 21, 2017. | Michael Hooper |
5/17/2018 | Cleanup Complete Determination Issued | DEC has issued a cleanup complete determination for this site after review of the administrative record. Remaining soil contamination is deeper than 15 feet and impacts to groundwater are extremely unlikely due to the depth of the aquifer. Additionally groundwater is not used as drinking water at this site. | Michael Hooper |
Contaminant Information
Name | Level Description | Media | Comments |
---|---|---|---|
DRO | Between Method 2 Migration to Groundwater and Human Health/Ingestion/Inhalation | Soil | DRO contamination remains at 15-18 ft below ground surface. |
Control Type
Type | Details |
---|---|
No ICs Required |
Requirements
Description | Details |
---|---|
Advance approval required to transport soil or groundwater off-site. | |
Movement or use of contaminated material (including on site) in a manner that results in a violation of the water quality standards is prohibited (18 AAC 70) |
Hazard ID | Site Name | File Number |
---|---|---|
25684 | FNSB - Weller Elementary School | 100.38.235 |