Skip to content Skip to content

Site Report: FNSB - Wescott Pool UST #2

Site Name: FNSB - Wescott Pool UST #2
Address: 300 East 8th Avenue, aka 2705 Old Richardson Highway, North Pole, AK 99705
File Number: 100.26.205
Hazard ID: 25682
Status: Cleanup Complete
Staff: No Longer Assigned, 9074655229 dec.icunit@alaska.gov
Latitude: 64.746324
Longitude: -147.343211
Horizontal Datum:WGS84

We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.

Problems/Comments

Underground storage tank #2, formerly storing diesel fuel, was removed on 7/20/2011. Observations during assessment activities indicated evidence of petroleum-contaminated soil due to releases from fill and vent pipes.

Action Information

Action Date Action Description DEC Staff
8/1/2011 Site Added to Database A new site has been added to the database Mitzi Read
8/1/2011 Spill Transferred from Prevention Preparedness and Response Program Spill transferred by PERP staff Ashley Anderson. Spill no. 11309920104; spill date = 7/20/11; substance = diesel; quantity = ~50 gallons. Mitzi Read
8/2/2011 Leaking Underground Storage Tank Release Confirmed - Petroleum LUST site created in CSP database for source area Diesel UST #2, 79110 Mitzi Read
11/21/2011 Document, Report, or Work plan Review - other DEC received and reviewed Wescott Memorial Pool Facility ID #1253 7,000-Gallon Diesel Underground Storage Tank Site Assessment/Tank Closure Report dated Nov 2011, prepared by ICA. The tank system was removed, recycled “as is” and disposed at the GNI yard. A new 4,000-gallon regulated duel heating oil and emergency use double-walled UST was installed in the same excavation. Approximately 107 cubic yards (cy) of contaminated soil was hauled offsite and thermally remediated. DRO contaminated soil (515 mg/kg), above the ADEC cleanup level, is confined to a small area on the south sidewall/bottom of the excavation. Approximately 40 cy of clean (below ADEC cleanup level) stockpiled soil and additional clean gravel were used used to backfill. (MBarnes) Willett Boger
12/31/2011 Leaking Underground Storage Tank Cleanup Initiated - Petroleum Administrative action addition for grant reporting purposes. Evonne Reese
1/31/2017 Potentially Responsible Party/State Interest Letter A PRP letter addressing several FNSB sites was mailed and the FNSB was notified. Michael Hooper
2/22/2017 Meeting or Teleconference Held Met with Borough Division of Public Works and briefly discussed the active FNSB CSP and LUST Sites. Preparing information request letter including 22 sites. Michael Hooper
4/25/2017 Update or Other Action Sent the FNSB a letter addressing 22 active CSP/UST sites. For The Wescott Pool UST 2 the letter requested information about abandoned UST piping and recommended options for additional contract work to address the remaining contamination Michael Hooper
6/23/2017 Update or Other Action Received a letter from the Borough with a contractor cost estimate for a phase 1 project scoping and file review for all active Fairbanks North Star Borough sites. Michael Hooper
9/12/2017 Update or Other Action Received phonecall from FNSB deputy director of public works. A report containing the information requested in the April 21, 2017 letter should be coming by end of October. Michael Hooper
11/9/2017 Update or Other Action Received memo with site summary in response to ADEC letter dated April 21, 2017. Michael Hooper
3/19/2021 Update or Other Action Sent Email regarding future requirements at Borough sites. Michael Hooper
8/10/2022 Site Characterization Workplan Approved Approved workplan for investigation of USTS 2&3. Site assessment and release investigation activities are proposed to investigate contamination found during closure by removal of UST#2 and to correct sampling deficiencies with the site assessment performed during change-in-service of UST#3. A direct push drill rig will be used to collect soil samples from four locations surrounding UST #3. Soil borings will be field screened with a photo-ionization detector and analytical samples will be collected from beneath piping and from the groundwater interface in accordance with 18 AAC 78.090. Based on field screening results, atleast one boring will be completed as a temporary groundwater sampling point to investigate impacts to groundwater. Michael Hooper
3/2/2023 Cleanup Complete Determination Issued Reviewed Former UST No. 2 and Deregulated/ Change-in-Service UST No. 3 Site Assessment/Site Characterization Report. Borings were advanced to groundwater. Soil samples were collected surrounding the tank. Soil at the location of Sample S3 previously exceeded the migration to groundwater cleanup level but appears to have attenuated to below detectable levels. Contamination was not detected in groundwater. Michael Hooper

Contaminant Information

Name Level Description Media Comments
DRO < Method 2 Most Stringent Soil

Control Type

Type Details
No ICs Required

Requirements

Description Details
Advance approval required to transport soil or groundwater off-site.
Movement or use of contaminated material (including on site) in a manner that results in a violation of the water quality standards is prohibited (18 AAC 70)
Hazard ID Site Name File Number
24299 FNSB - Wescott Pool 100.26.038
23415 FNSB - NORTH POLE MIDDLE SCHOOL UST 1 100.26.080
25702 FNSB - North Pole Middle School UST #2 100.26.212

Missing Location Data

Because the GIS location data for this site has not been entered, we cannot direct you to its position on the map. Click "Continue" to proceed to the Contaminated Sites Web Map or "Close" to return to the site report.
Continue     Close