Site Report: Commercial Property - 19 College Road / Tax Lot 221
Site Name: | Commercial Property - 19 College Road / Tax Lot 221 |
---|---|
Address: | 19 College Road, Fairbanks, AK 99701 |
File Number: | 102.26.173 |
Hazard ID: | 26138 |
Status: | Cleanup Complete |
Staff: | No Longer Assigned, 9074655229 dec.icunit@alaska.gov |
Latitude: | 64.849297 |
Longitude: | -147.703194 |
Horizontal Datum: | WGS84 |
![]() | ![]() |
![]() | ![]() |
We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.
Problems/Comments
In May 2013 environmental sampling was conducted as part of a change-in-service for a 5,000-gallon diesel underground storage tank (Owner Tank ID #1 / DEC Tank ID #2) from a regulated emergency power generator fuel tank to a non-regulated heating oil tank. DRO was detected in soil and DRO and naphthalene were detected in groundwater, all at levels below the most stringent DEC cleanup levels.
Action Information
Action Date | Action | Description | DEC Staff |
---|---|---|---|
10/24/2013 | Site Added to Database | A new site has been added to the database | Mitzi Read |
10/24/2013 | Leaking Underground Storage Tank Release Confirmed - Petroleum | LUST site created in CSP database for source area 5,000-Gallon Diesel UST (Owner Tank ID #1 / DEC Tank ID #2), 79530 | Mitzi Read |
10/31/2013 | Potentially Responsible Party/State Interest Letter | Bill Janes | |
4/22/2014 | Update or Other Action | Reviewed the site characterization report from Travis/Peterson Consulting. Characterization consisted of soil and groundwater sampling from four borings installed with Geoprobe - three of these borings were advanced to groundwater. Samples were analyzed for BTEX, GRO, DRO, and PAHs. DRO was detected in soil and DRO and napthalene were detected in groundwater; however, all sampling results were below ADEC cleanup levels. TPECI and Inland Petroservice tested the vent line and the tank fill port secondary containment collar. One aboveground coupling in the vent line leaked and was tightened. | Janice Wiegers |
4/24/2014 | Cleanup Complete Determination Issued | Cleanup letter sent to North Arctic Trust, LLC. | Janice Wiegers |
6/30/2014 | Leaking Underground Storage Tank Cleanup Initiated - Petroleum | Administrative action addition for grant reporting purposes. | Evonne Reese |
10/29/2014 | Institutional Control Record Removed | Institutional Controls have been removed. | Janice Wiegers |
Contaminant Information
Name | Level Description | Media | Comments |
---|---|---|---|
DRO | < Method 2 Most Stringent | Soil | |
DRO | < Table C | Groundwater | |
Naphthalene | < Table C | Groundwater |
Control Type
Type | Details |
---|---|
No ICs Required |
Requirements
Description | Details |
---|---|
Advance approval required to transport soil or groundwater off-site. |
Hazard ID | Site Name | File Number |
---|---|---|
3961 | Bentley Trust Property Tax Lot 221 | 100.38.166 |