Site Report: Bay Crest Fuel & C Store
Site Name: | Bay Crest Fuel & C Store |
---|---|
Address: | 3375 Sterling Highway, Homer, AK 99603 |
File Number: | 2314.26.035 |
Hazard ID: | 26143 |
Status: | Cleanup Complete |
Staff: | No Longer Assigned, 9074655229 dec.icunit@alaska.gov |
Latitude: | 59.658083 |
Longitude: | -151.638802 |
Horizontal Datum: | WGS84 |
We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.
Problems/Comments
On September 19, 2013 during an Environmental Site Assessment conducted by Tesoro Refining and Marketing Company, benzene soil contamination was encountered south of the two underground storage tanks (one 26,000 and one 20,000-gallon tanks) at 0.326, 0.136 and 0.178 mg/kg at depths of 10 to 17.5 feet below ground surface. The facility has an on-site water well drilled to a depth of 184 feet. This water is filtered, treated and then plumbed only to the exterior spigot on the east side of the building, where it is used solely for non-potable water. The station is serviced by potable water trucked in from the City of Homer public water system, and stored in a 1,000-gallon above ground water storage tank. Water collected from the spigot on the east side of the building was sampled with detectable levels of GRO, DRO, BTEX, Naphthalene, and PCE, none at concentrations exceeding Alaska drinking water standards for public water systems.
Action Information
Action Date | Action | Description | DEC Staff |
---|---|---|---|
11/1/2013 | Site Added to Database | A new site has been added to the database | Alyce Hughey |
11/1/2013 | Leaking Underground Storage Tank Release Confirmed - Petroleum | LUST site created in CSP database for source area Underground Storage Tank, 79534 | Alyce Hughey |
11/1/2013 | Exposure Tracking Model Ranking | Initial ranking with ETM completed for source area id: 79534 name: Underground Storage Tank | Alyce Hughey |
11/6/2013 | Potentially Responsible Party/State Interest Letter | Bill Janes | |
1/17/2014 | Document, Report, or Work plan Review - other | Received Coble Geophysical Service's revised Work Plan, Contaminated Soil Cleanup, for ADEC review. | Paul Horwath |
2/1/2014 | Leaking Underground Storage Tank Cleanup Initiated - Petroleum | Administrative action addition for grant reporting purposes. | Evonne Reese |
2/18/2014 | Site Characterization Workplan Approved | Paul Horwath approved the January 17, 2014, Coble Geophysical Service's revised Work Plan, Contaminated Soil Cleanup, for the Bay Crest Fuel & C Store, revised by ADEC as of 1/21/14. | Alyce Hughey |
5/28/2014 | Exposure Tracking Model Ranking | A new updated ranking with ETM has been completed for source area 79534 Underground Storage Tank. | Paul Horwath |
5/29/2014 | Cleanup Complete Determination Issued | Based on the environmental characterization work completed at this site, ADEC has determined that the residual contamination doesn’t pose an unacceptable risk to human health or the environment. Therefore, a Cleanup Complete determination is issued, subject to the following condition: The most current soil sample analytical data from this site reported DRO and benzene contamination exceeding the ADEC ‘Migration to Groundwater’ soil cleanup levels at depths of 10 to 27 feet below ground surface south/southwest of the two underground fuel storage tanks. Any proposal to excavate, transport, move, treat, and/or dispose of contaminated soil at this “site” requires prior ADEC approval. This is consistent with the requirements of 18 AAC 78.274(b) and 18 AAC 78.600(h). A “site” [as defined by 18 AAC 75.990 (115)] means an area that is contaminated, including areas contaminated by the migration of hazardous substances from a source area, regardless of property ownership. | Paul Horwath |
Contaminant Information
Name | Level Description | Media | Comments |
---|---|---|---|
Benzene | Between Method 2 Migration to Groundwater and Human Health/Ingestion/Inhalation | Soil | |
DRO | Between Method 2 Migration to Groundwater and Human Health/Ingestion/Inhalation | Soil |
Control Type
Type | Details |
---|---|
No ICs Required |
Requirements
Description | Details |
---|---|
Advance approval required to transport soil or groundwater off-site. |
No associated sites were found.