We make every effort to ensure the data presented here is accurate based on the best available information currently on file with DEC. It is therefore subject to change as new information becomes available. We recommend contacting the assigned project staff prior to making decisions based on this information.

Problems/Comments

While manually filling a day tank on the south side of the Z Annex building at the FAA Anchorage Air Route Traffic Control Center ZAN the operator was away from the tank and it overfilled. Subsequently the U.S. government shut down caused employees to be away from the facility and the fuel was not removed from secondary containment. It rained a significant amount during October 2013, and when FAA employees returned they found that the fuel had pressured out of secondary containment area and spilled onto the ground. The spill amount was estimated between 50-60 gallons. A subcontractor working on an adjacent tank removal project could not remove all of the contamination due to poor material causing cave in of the excavation; they were able to excavate to approximately 7 feet bgs. Remaining area of contaminated soil, estimated at 2 feet square, contains 752 mg/kg DRO.

Action Information

Action Date Action Description DEC Staff
11/5/2013 Spill Transferred from Prevention Preparedness and Response Program Spill transferred by PERP staff Shannon DeWandel. Spill no. 13239927703; spill date = 10/4/13; substance = diesel; quantity = ~50-60gallons; source = day tank overfill, release from secondary containment. Mitzi Read
12/3/2013 Site Added to Database A new site has been added to the database Mitzi Read
12/3/2013 Exposure Tracking Model Ranking Initial ranking with ETM completed for source area id: 79564 name: Day Tank Overfill - Diesel Mitzi Read
2/6/2017 Potentially Responsible Party/State Interest Letter Sent PRP Letter to FAA Erin Gleason
2/6/2017 Update or Other Action draft report dispenser removal and UST piping upgrade site assessment report federal aviation administration air route traffic control center Anchorage, Alaska dated May 19, 2016 by Ahtna Environmental. According to the information provided in the report, additional contamination was detected at the FAA Anchorage air traffic control center. This contamination is association with the two 10,000 gallon unregulated diesel underground storage tanks (UST) and their piping. The tanks are listed as #6 and #7 at facility 0251 in the ADEC UST database. Erin Gleason
2/6/2017 Update or Other Action Letter sent to FAA requesting the lab data, QA/QC checklist, and soil disposal receipts from the May 2016 report. Due April 2017. Erin Gleason
2/6/2017 Update or Other Action Letter sent to FAA requesting characterization work plan. Erin Gleason
2/21/2017 Meeting or Teleconference Held Phone conference with Jon Schleder at FAA. FAA will request funding for this site for FY 2018 or FY 2019. Erin Gleason
5/9/2017 Update or Other Action Received missing item from the May 19, 2016 report. D Wagstaffe of Parsons emailed ADEC the soil receipts, full data report, and laboratory checklist. Erin Gleason
5/24/2017 Site Characterization Report Approved May 19, 2016 report is complete and approved. Data gaps for the site still remain. ADEC's UST program still has open and active case that requires further characterization, separate from the contaminated site requirements. Erin Gleason
6/6/2018 Update or Other Action Received email from Aemon Wetmore at FAA. There is no work schedule at this time. Erin Gleason
2/5/2019 Update or Other Action Emailed FAA requesting an update for when the site will receive work. Erin Gleason
6/29/2020 Document, Report, or Work plan Review - other Received draft work plan from FAA on 5/21/2020. ADEC has reviewed the work plan and requests revisions. Letter sent to FAA on this date. Erin Gleason
7/15/2020 Document, Report, or Work plan Review - other ADEC received response to comments (RTC) from FAA on 7/15/2020. ADEC has reviewed the RTC and agrees. ADEC requests the final draft work plan be submitted. Erin Gleason
8/17/2020 Site Characterization Workplan Approved ADEC received the revise work plan. It is now approved. Erin Gleason
4/1/2022 Document, Report, or Work plan Review - other Review of Engine Generator Room Site Investigation report completed and comments provided to FAA. Report details the advancement of soil borings within the Engine Generator Room to determine if soils underlying the concrete slab were contaminated. No analytes above DEC's Method Two Soil Cleanup Levels were detected. Kelly Walker

Contaminant Information